Home » Categories » Protocols » Ethernet

What Ethernet ports are required for Prosoft PLC modules and gateways?

Prosoft gateways and in-chassis PLC modules which are configured via Ethernet use UDP port 50000 for discovery and UDP port 3000 for configuration and online diagnostics.

Web based services for products including AN-X2 and Fieldserver gateways require TCP port 80

Some of the more common ports required for application protocols are:

TCP 502  Modbus TCP - MBTCP, MNET products

TCP 44818 Ethernet/IP - EIP and DFNT products

UDP 44818 Ethernet/IP - EIP and DFNT products

TCP 2222  Allen Bradley CSP protocol - Fieldserver

TCP 2000 Encapulated Modbus TCP - Typically used for Modbus TCP through serial to Ethernet media converters with MBTCP and MNET products.

TCP 20000 DNP3 over Ethernet - DNPNET, DNPSNET products

UDP 20000 DNP3 over Ethernet - DNPNET, DNPSNET products

UDP 47808 BACNET IP - Slotserver and Fieldserver BACNET products

UDP 1024  Fieldserver discovery service - Slotserver and Fieldserver products

UDP 18246 GE Ethernet Global Data - All EGD modules and gateways. Note that EGD exchanges may be unicast, multicast, or broadcast


Custom Fields