Can the MVI56-xx modules be placed in a remote rack? |
| Article Number: 69 | Rating: 3/5 from 1 votes | Last Updated: Tue, Jul 1, 2014 at 12:00 AM |
|
Generally, yes. When using ControlNet to access the remote chassis, however, I/O bandwidth limitation may become an issue. Because the MVI56 modules requires 250 words of inputs, and 248 words of output, the ControlNet bandwidth may not be sufficient to handle this depending on the other I/O module in the remote chassis with the MVI56 module. Increasing the RPI in the I/O properties for the module as well as the remote ControlNet adapter tends to help alleviate the problem but a better choice, where available, would be one of our reduced I/O modules which offer a reduced I/O image of 42 words of input, and 42 words of output. For serial Modbus communications, we offer the MVI56E-MCMR For Modbus TCP, we offer the MVI56E-MNETR (client/server) and MVI56E-MNETCR (client only) For DF1 communications, we offer the MVI56-DFCMR, which uses the same I/O size as the MCMR. For 103M communications, we offer the MVI56-103MR, which uses the same I/O size as the MCMR. For DH485 communications, we offer the MVI56-DH485R, which uses the same I/O size as the MCMR. For all other MVI56 modules, if ControlNet bandwidth is an issue, then our recommendation is to include an Ethernet/IP connection to the remote chassis for access to the MVI56 modules.
Related Keywords: MVI56, MVI56E, ControlNet, RSNetworx, redundant |
Attachments (0)
There are no attachments for this article.
|
Comments
There are no comments for this article. Be the first to post a comment.
|
Debug port connection parameters for Prosoft modules and gateways
Viewed 1 times since Tue, Nov 28, 2006
Can the MVI56-WA-EIP be used to acquire I/O data from a ControlLogix CPU from a remote rack?
Viewed 1 times since Wed, Feb 6, 2008
What RSLogix 5000 function will indicate whether a Prosoft module is present and functioning in the ControlLogix chassis?
Viewed 1 times since Tue, Nov 28, 2006
What is the backplane current draw for MVI56, MVI56E, MVI69, MVI46 and MVI71 modules?
Viewed 1 times since Thu, Jan 10, 2008
What are Optional AOIs and do I need them?
Viewed 1 times since Tue, Jun 7, 2016
What is the heat dissapation for MVI56, MVI56E, MVI69, MVI46 and MVI71 modules?
Viewed 1 times since Thu, Jan 10, 2008
I have an In-Chassis module, and am seeing a type mismatch shown in the module properties. What is the issue?
Viewed 1 times since Fri, Apr 27, 2007
"Invalid Input Size" when adding an Prosoft module to RSLogix 5000
Viewed 1 times since Tue, Nov 28, 2006
The BATT LED on my ProSoft MVI module is RED. How can I fix this problem?
Viewed 1 times since Wed, Nov 29, 2006
Why do I have a yellow question mark in the RSWho window or in RSNetworx for my MVI56 Series module?
Viewed 1 times since Tue, Nov 28, 2006
|

Add Comment