Can the MVI56-xx modules be placed in a remote rack? |
Article Number: 69 | Rating: 3/5 from 1 votes | Last Updated: Tue, Jul 1, 2014 at 12:00 AM |
Generally, yes. When using ControlNet to access the remote chassis, however, I/O bandwidth limitation may become an issue. Because the MVI56 modules requires 250 words of inputs, and 248 words of output, the ControlNet bandwidth may not be sufficient to handle this depending on the other I/O module in the remote chassis with the MVI56 module. Increasing the RPI in the I/O properties for the module as well as the remote ControlNet adapter tends to help alleviate the problem but a better choice, where available, would be one of our reduced I/O modules which offer a reduced I/O image of 42 words of input, and 42 words of output. For serial Modbus communications, we offer the MVI56E-MCMR For Modbus TCP, we offer the MVI56E-MNETR (client/server) and MVI56E-MNETCR (client only) For DF1 communications, we offer the MVI56-DFCMR, which uses the same I/O size as the MCMR. For 103M communications, we offer the MVI56-103MR, which uses the same I/O size as the MCMR. For DH485 communications, we offer the MVI56-DH485R, which uses the same I/O size as the MCMR. For all other MVI56 modules, if ControlNet bandwidth is an issue, then our recommendation is to include an Ethernet/IP connection to the remote chassis for access to the MVI56 modules.
Related Keywords: MVI56, MVI56E, ControlNet, RSNetworx, redundant |
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
Debug port connection parameters for Prosoft modules and gateways
Viewed 1 times since Tue, Nov 28, 2006
"Invalid Input Size" when adding an Prosoft module to RSLogix 5000
Viewed 1 times since Tue, Nov 28, 2006
When saving a project including a ControlNet network in RSLogix5000 v18, a warning message appears - "Warning: Failed to create new device in ControlNet project file. Generic module cannot be created." What does this mean?
Viewed 1 times since Tue, Jul 27, 2010
I have an In-Chassis module, and am seeing a type mismatch shown in the module properties. What is the issue?
Viewed 1 times since Fri, Apr 27, 2007
I upgraded my RSLogix5000 software from an older version to Version 16 and now the clock in my MVI56 module does not seem to show the correct time. Why not?
Viewed 1 times since Tue, Oct 14, 2008
Why do I have a yellow question mark in the RSWho window or in RSNetworx for my MVI56 Series module?
Viewed 1 times since Tue, Nov 28, 2006
What RSLogix 5000 function will indicate whether a Prosoft module is present and functioning in the ControlLogix chassis?
Viewed 1 times since Tue, Nov 28, 2006
My ControlNet network shows a maximum usage value of 99.61% when an MVI56-XXX or MVI56E-XXX is in the rack, why is this?
Viewed 1 times since Fri, Oct 15, 2010
What are Optional AOIs and do I need them?
Viewed 1 times since Tue, Jun 7, 2016
What is the heat dissapation for MVI56, MVI56E, MVI69, MVI46 and MVI71 modules?
Viewed 1 times since Thu, Jan 10, 2008
|