Home » Categories » Multiple Categories |
What driver should be used in RSLinx Classic to browse or get data from PLC5 or SLC controllers on a DH+ network? |
Article Number: 517 | Rating: Unrated | Last Updated: Tue, Aug 5, 2014 at 5:58 PM |
The best driver to use in RSLinx Classic is the Ethernet Devices driver. Specify the IP Address of the AN-X(2)-AB-DHRIO gateway in the driver configuration. The gateway emulates a 4 slot ControlLogix chassis with an ethernet module and a DH+ bridge module in the chassis (with just the A channel): |
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
How many Data Highway Plus Nodes can a single AN-X2-AB-DHRIO communicate with?
Viewed 1 times since Tue, Aug 18, 2015
Do AN-X2-AB-DHRIO work with redundant control logix processors?
Viewed 1 times since Mon, Aug 24, 2015
ControlLogix, CompactLogix, and SLC Message Samples through the AN-X(2) DH+ gateway
Viewed 1 times since Thu, Jun 19, 2014
Can an AN-X2-AB-DHRIO communicate with a 1756-DHRIO
Viewed 1 times since Tue, Sep 29, 2015
What OPC Servers will work with the AN-X(2)-AB-DHRIO gateway running the DH+ firmware?
Viewed 1 times since Tue, Aug 5, 2014
What are common things that prevent reliable DH+ communications on the AN-X(2)-AB-DHRIO gateway running the DH+ Bridge FW?
Viewed 1 times since Wed, Dec 31, 2014
How can I use an AN-X2-AB-DHRIO to allow a SLC5/04 on DH+ to talk to a Panel View Plus on EtherNet/IP
Viewed 1 times since Fri, Aug 28, 2015
|