What are common things that prevent reliable DH+ communications on the AN-X(2)-AB-DHRIO gateway running the DH+ Bridge FW? |
Article Number: 536 | Rating: Unrated | Last Updated: Thu, Feb 26, 2015 at 3:13 PM |
If the NS or NET LED is not solid green then check the recommendations below:
1) For networks running at 57k6 or 115k2 bauds it is necessary to have 150 ohm resistors on each end of the network (for 230k4 use 82 ohm resistors) |