I was not using both Modbus ports on my MVI56-MCM module, so I set all the port parameters for the unused port to zeros to disable the port and now my module is faulted and will not restart. Why? |
Article Number: 162 | Rating: Unrated | Last Updated: Thu, Jul 17, 2014 at 4:25 PM |
On some older modules, setting the baud rate to zero for either Modbus port will cause the entire module to fault. Modbus ports on the MVI56 can be individually enabled or disabled using the controller tag mcm.portx.enabled, where x=the port number in the controller tags mcm table. Setting to zero (0) disables the port. setting to (1) enables the port. If this value is set to zero (0), disabling the port, the rest of the parameters can be left as is because the port will not be active. just be sure the tag mcm.portx.baudrate is a valid baud rate and not zero (0). |
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
When I increase the ReadData or WriteData array sizes in my program, all of the configuration parameter values go to 0.
Viewed 1 times since Tue, Nov 28, 2006
Apparent data corruption in 33 words of MVI56-MCM or MVI56E-MCM ReadData or WriteData arrays.
Viewed 1 times since Tue, Nov 28, 2006
Bulletin 1-5165141 MVI56-MCM getting intermittent communications errors when operating on both ports
Viewed 1 times since Wed, Nov 29, 2006
How can I configure the module to store and initialize input values on reset or powerup?
Viewed 1 times since Tue, Nov 28, 2006
Where is the configuration for the MVI56(E)-MCM?
Viewed 1 times since Wed, Jul 9, 2014
Where are the on-board jumper positions defined for my MVI module?
Viewed 1 times since Tue, Nov 28, 2006
Which of your products support RS-485 serial protocols?
Viewed 1 times since Wed, Feb 6, 2008
What causes a conditional command to be issued?
Viewed 1 times since Tue, Nov 28, 2006
Do the serial ports on my MVI56 module provide any electrical isolation?
Viewed 1 times since Tue, Nov 28, 2006
How to avoid slow data updates on a Modbus network with an MVI56(E)-MCM or MVI69-MCM when some Slaves are either not on-line or not functioning correctly?
Viewed 1 times since Wed, Mar 19, 2008
|