Home » Categories » Rockwell In-chassis » ControlLogix » MVI56 Series » MVI56-MCM |
Bulletin 1-5165141 MVI56-MCM getting intermittent communications errors when operating on both ports |
Article Number: 277 | Rating: 2/5 from 3 votes | Last Updated: Thu, Jul 17, 2014 at 4:01 PM |
Version 1.26 of the MVI56-MCM module firmware has been created to address this issue. This new version of code uses interrupt timing, to drop the RTS line as quick as possible, and enable the module to be ready to receive messages as fast as it can. All previous versions of the module should be flash updated to this new version, as this has been proven to increase reliability of all modbus master and modbus slave applications at all baud rates. this will also eliminate the need for customer's to setup the guard band parameter for issuing write messages as a master, or on multi-drop slave applications. |
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
What causes a conditional command to be issued?
Viewed 1 times since Tue, Nov 28, 2006
Where are the on-board jumper positions defined for my MVI module?
Viewed 1 times since Tue, Nov 28, 2006
Apparent data corruption in 33 words of MVI56-MCM or MVI56E-MCM ReadData or WriteData arrays.
Viewed 1 times since Tue, Nov 28, 2006
Where is the configuration for the MVI56(E)-MCM?
Viewed 1 times since Wed, Jul 9, 2014
Which of your products support RS-485 serial protocols?
Viewed 1 times since Wed, Feb 6, 2008
When I increase the ReadData or WriteData array sizes in my program, all of the configuration parameter values go to 0.
Viewed 1 times since Tue, Nov 28, 2006
How to avoid slow data updates on a Modbus network with an MVI56(E)-MCM or MVI69-MCM when some Slaves are either not on-line or not functioning correctly?
Viewed 1 times since Wed, Mar 19, 2008
Do the serial ports on my MVI56 module provide any electrical isolation?
Viewed 1 times since Tue, Nov 28, 2006
I was not using both Modbus ports on my MVI56-MCM module, so I set all the port parameters for the unused port to zeros to disable the port and now my module is faulted and will not restart. Why?
Viewed 1 times since Tue, Nov 28, 2006
What is the difference between the MVI56-MCM and the MVI56-MCMR?
Viewed 1 times since Tue, Nov 28, 2006
|