Apparent data corruption in 33 words of MVI56-MCM or MVI56E-MCM ReadData or WriteData arrays. |
| Article Number: 182 | Rating: 5/5 from 1 votes | Last Updated: Thu, Jul 17, 2014 at 4:22 PM |
|
In your controller tags, if MCM.Config.ModDef.ErrStatPtr is 0, then status data is likely overwriting the first 33 words of the MCM's ReadData or WriteData arrays which would typically be used for Modbus data. |
Attachments (0)
There are no attachments for this article.
|
Comments
There are no comments for this article. Be the first to post a comment.
|
What is the difference between the MVI56-MCM and the MVI56-MCMR?
Viewed 1 times since Tue, Nov 28, 2006
How to avoid slow data updates on a Modbus network with an MVI56(E)-MCM or MVI69-MCM when some Slaves are either not on-line or not functioning correctly?
Viewed 1 times since Wed, Mar 19, 2008
Do the serial ports on my MVI56 module provide any electrical isolation?
Viewed 1 times since Tue, Nov 28, 2006
Which of your products support RS-485 serial protocols?
Viewed 1 times since Wed, Feb 6, 2008
When I increase the ReadData or WriteData array sizes in my program, all of the configuration parameter values go to 0.
Viewed 1 times since Tue, Nov 28, 2006
Bulletin 1-5165141 MVI56-MCM getting intermittent communications errors when operating on both ports
Viewed 1 times since Wed, Nov 29, 2006
What is the purpose of the UseGuardBand/GuardBandTime or InterCharacterDelay parameters in an MCM module?
Viewed 1 times since Tue, Nov 28, 2006
I was not using both Modbus ports on my MVI56-MCM module, so I set all the port parameters for the unused port to zeros to disable the port and now my module is faulted and will not restart. Why?
Viewed 1 times since Tue, Nov 28, 2006
Where are the on-board jumper positions defined for my MVI module?
Viewed 1 times since Tue, Nov 28, 2006
Where is the configuration for the MVI56(E)-MCM?
Viewed 1 times since Wed, Jul 9, 2014
|

Add Comment