Apparent data corruption in 33 words of MVI56-MCM or MVI56E-MCM ReadData or WriteData arrays. |
Article Number: 182 | Rating: 5/5 from 1 votes | Last Updated: Thu, Jul 17, 2014 at 4:22 PM |
In your controller tags, if MCM.Config.ModDef.ErrStatPtr is 0, then status data is likely overwriting the first 33 words of the MCM's ReadData or WriteData arrays which would typically be used for Modbus data. |
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
What causes a conditional command to be issued?
Viewed 1 times since Tue, Nov 28, 2006
I was not using both Modbus ports on my MVI56-MCM module, so I set all the port parameters for the unused port to zeros to disable the port and now my module is faulted and will not restart. Why?
Viewed 1 times since Tue, Nov 28, 2006
What is the difference between your MVI56E-MCM and MVI56E-MCMR modules?
Viewed 1 times since Tue, Jan 23, 2007
Where are the on-board jumper positions defined for my MVI module?
Viewed 1 times since Tue, Nov 28, 2006
When I increase the ReadData or WriteData array sizes in my program, all of the configuration parameter values go to 0.
Viewed 1 times since Tue, Nov 28, 2006
Which of your products support RS-485 serial protocols?
Viewed 1 times since Wed, Feb 6, 2008
Do the serial ports on my MVI56 module provide any electrical isolation?
Viewed 1 times since Tue, Nov 28, 2006
Which ProSoft products can communicate with a Honeywell DCS System?
Viewed 1 times since Tue, Jan 22, 2008
Where is the configuration for the MVI56(E)-MCM?
Viewed 1 times since Wed, Jul 9, 2014
How to configure more than 100 commands per port when using an MVI46-MCM, MVI69-MCM, or the MVI56-MCM as a Modbus master?
Viewed 1 times since Tue, Nov 28, 2006
|