I have a PROFIBUS DP network with ProSoft PROFIBUS DP Master solution that appears to be operating normally (no bus faults, slaves report "OK"), but I am unable to control my devices. What

Many things can result in these symptoms.  One of the most common causes is that not all slave manufacturers use a standard byte order.  It is very possible that when you think you're sending a value of "1" to a slave's bit address 0, you may be sending a "1" to the slave's bit address 8. 

Enabling the Swap Input/Output Byte parameter would resolve the issue in this case.

Custom Fields
    Attachments (0) Attachments
    There are no attachments for this article.
    Comments Comments
    There are no comments for this article. Be the first to post a comment.
    Related Articles RSS Feed
    How to resolve an issue where Siemens Step 7 software displays a message indicating that the ProSoft GSD file cannot be interpreted.
    Viewed 1 times since Wed, Nov 29, 2006
    I need to set up a ProSoft PROFIBUS Master to talk to a Siemens S7-300 series CPU that is set up as a PROFIBUS Slave. How do I do that?
    Viewed 1 times since Mon, Feb 18, 2008
    Does ProSoft or ProLinx support Profibus PA?
    Viewed 1 times since Tue, Nov 28, 2006
    My Profibus Master (PDPMV1) card is not communicating and will not go into RUN mode but does not show an error in the ProSoft Configuration Builder software, why?
    Viewed 1 times since Thu, Apr 7, 2011
    Can a ProSoft PROFIBUS DP v1 Master solution also be configured as a Slave to another Master?
    Viewed 1 times since Wed, Mar 5, 2008
    I am trying to download my PROFIBUS PDPMV1 Master/Slave configuration from the ProSoft Configuration Builder (PCB) "PROFIBUS - PDPMV1" Online-Download Configuration menu option; and it is lo
    Viewed 1 times since Tue, Mar 18, 2008
    Can a ProSoft PROFIBUS DP v1 Master solution communicate directly with other PROFIBUS DP v1 Masters?
    Viewed 1 times since Wed, Mar 5, 2008
    I can't get my ProSoft PROFIBUS DP V1 Master to talk to all of the Slave Nodes on my PROFIBUS network. What might the problem be?
    Viewed 1 times since Thu, Sep 4, 2008
    How can I monitor module and slave status with the MVI56-PDPV1 and other PDPMV1 PROFIBUS master modules?
    Viewed 1 times since Wed, Nov 29, 2006
    How do I setup my 3170-PDP in Step 7 software?
    Viewed 1 times since Tue, Nov 28, 2006