| Home » Categories » Protocols » Modbus |
My RX light is on solid, what might that indicate? |
| Article Number: 561 | Rating: Unrated | Last Updated: Fri, Jul 17, 2015 at 10:32 PM |
|
If the RX light is on solid on your modbus serial port and: The port is in RS485 mode- This is usually indicative of polarity being reversed (ie. positive is connected to negative instead of positive to positive). Try swapping the wiring to pins 1 and 8 on our port. The port is in RS232 mode- This suggests that a constant electrical signal is hitting our receive pin which should never occur during normal operation. We have seen this on occasion with customer USB to serial converters which are not set up correctly, we strongly recommend trouble shooting your USB to serial converter if this is the case. If there is no converter involved, we recommend verifying the wire connected to our RX pin is connected to the correct pin on the other device. If none of these common causes seem to be causing your RX to be on solid, please call Prosoft Technical Support to trouble shoot your issue further. |
Attachments (0)
There are no attachments for this article.
|
Comments
There are no comments for this article. Be the first to post a comment.
|
Do any Prosoft modules support Modbus UDP?
Viewed 1 times since Mon, Aug 24, 2015
I have multiple Modbus masters that need to communicate with 1 or more Modbus serial (RTU) slave devices. What product should be used??
Viewed 1 times since Tue, Jan 23, 2007
What's the difference between Modbus ASCII and Modbus RTU?
Viewed 1 times since Wed, Mar 19, 2008
I have limited or no experience with Modbus. How can I find out more about the protocol and command structure?
Viewed 1 times since Tue, Nov 28, 2006
I am trying to use a ProSoft Modbus solution to send/receive data to a MSA Ultima X gas dectection system with Modbus interface and am having problems. How can I resolve this issue?
Viewed 1 times since Thu, Apr 24, 2008
How do I read/write Modbus binary data?
Viewed 1 times since Wed, Nov 29, 2006
If I am reading the value from ProSoft 4x register, and it represents a digital input or digital output, how is the value stored?
Viewed 1 times since Tue, Nov 28, 2006
Read Commands from my Modbus Master to a ProSoft MCM Slave are working but Write Commands are failing. How do I fix this?
Viewed 1 times since Fri, Feb 8, 2008
How can I detect the feedback status of individual command successful or failed?
Viewed 1 times since Wed, Nov 29, 2006
How do I monitor the health of coms to my slaves when the module is a Master?
Viewed 1 times since Wed, Nov 29, 2006
|

Add Comment