My RX light is on solid, what might that indicate? |
Article Number: 561 | Rating: Unrated | Last Updated: Fri, Jul 17, 2015 at 10:32 PM |
If the RX light is on solid on your modbus serial port and: The port is in RS485 mode- This is usually indicative of polarity being reversed (ie. positive is connected to negative instead of positive to positive). Try swapping the wiring to pins 1 and 8 on our port. The port is in RS232 mode- This suggests that a constant electrical signal is hitting our receive pin which should never occur during normal operation. We have seen this on occasion with customer USB to serial converters which are not set up correctly, we strongly recommend trouble shooting your USB to serial converter if this is the case. If there is no converter involved, we recommend verifying the wire connected to our RX pin is connected to the correct pin on the other device. If none of these common causes seem to be causing your RX to be on solid, please call Prosoft Technical Support to trouble shoot your issue further. |
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
I have multiple Modbus masters that need to communicate with 1 or more Modbus serial (RTU) slave devices. What product should be used??
Viewed 1 times since Tue, Jan 23, 2007
How can a module's Modbus port, configured as a Slave port, detect communication loss with the Master port?
Viewed 1 times since Tue, Nov 28, 2006
Do any Prosoft modules support Modbus UDP?
Viewed 1 times since Mon, Aug 24, 2015
I have a ProSoft Modbus Master solution and would like to know, is the Slave Status List the best place to monitor for communications health of the network?
Viewed 1 times since Tue, Mar 18, 2008
If I am reading the value from ProSoft 4x register, and it represents a digital input or digital output, how is the value stored?
Viewed 1 times since Tue, Nov 28, 2006
What's the difference between Modbus ASCII and Modbus RTU?
Viewed 1 times since Wed, Mar 19, 2008
What are the causes of a -11 error code using a ProSoft Modbus product?
Viewed 1 times since Mon, May 17, 2010
How do you detect the individual Slave failure?
Viewed 1 times since Wed, Nov 29, 2006
What Modbus address would we need to put into the MODSIM32 simulator if we specified on the MVI56-MCM device address to 8680HEX (-31104 decimal) when the MVI56-mcm is the slave?
Viewed 1 times since Tue, Nov 28, 2006
Defining the Slave ID when issuing Modbus Broadcast write commands
Viewed 1 times since Tue, Nov 28, 2006
|