| Home » Categories » Multiple Categories |
Cannot Download from PC to Device in ProSoft Configuration Builder |
| Article Number: 593 | Rating: Unrated | Last Updated: Tue, Dec 8, 2015 at 8:51 PM |
|
When changing the IP address of a Modbus TCP module, the "Download from PC to Device" option can be grayed out if there are Modbus Master commands with IP addresses that still reference the old IP Address subnet. In this case the configuration is assumed invalid due to the fact that the commands still reference the old subnet. Update the Master commands, and the "Download from PC to Device" option will become available again, once the configuration has passed validation by ProSoft Configuration Builder.
Note: This behavior is not noticed if the option to "Disable Range Checking Functionality" under Tools->Options, is CHECKED, which is not recommended by ProSoft Technical Support. |
Attachments (0)
There are no attachments for this article.
|
Comments
There are no comments for this article. Be the first to post a comment.
|
How do I get Floating Point (or Double INT or Unsigned INT) data?
Viewed 1 times since Wed, Nov 29, 2006
How does the gateway know where to load or store configuration files (SD card or non-volatile RAM)?
Viewed 1 times since Mon, Sep 29, 2014
Does ProSoft Configuration Builder run in Windows 7/8/10?
Viewed 1 times since Wed, Jun 25, 2014
I am trying to connect to the Debug/Configuration port using HyperTerminal on Windows Vista. How can I do this?
Viewed 1 times since Thu, Apr 9, 2009
Why am I unable to download a configuration file to a 4xxx or 5xxx Series gateway, and the Debug Port LED is on?
Viewed 1 times since Fri, Jun 27, 2014
Why are my PLX gateway modbus serial commands not executing despite being enabled?
Viewed 1 times since Wed, Aug 12, 2015
Can I configure my ProLinx 4xxx or 5xxx series gateway via Ethernet?
Viewed 1 times since Tue, Nov 28, 2006
Can the FIFO buffer settings on my Windows PC COM Ports affect communications to In-Chassis modules and 5000 series gateways?
Viewed 1 times since Tue, Jul 8, 2008
Prosoft Configuration Builder (PCB) runtime errors: "SideBySide" or VC++ files not found
Viewed 1 times since Mon, Jun 24, 2013
Differences between the PLX31 & PLX32 Gateways
Viewed 1 times since Fri, Jul 10, 2015
|

Add Comment