How do I setup the DNPSNET module to perform unsolicited messaging?
Viewed 1 times since Tue, Nov 28, 2006
In order to use unsolicited messaging on an In-Chassis DNP application, your client (DNP master) will need to be connected to via a TCP/IP connection. All DNP Ethernet devices must support both TCP/IP and UDP for their transport layers. Since TCP/IP... Read More
How to control binary outputs using the MVI56E-DNPNET client
Viewed 1 times since Thu, Jul 17, 2014
While most DNP commands are defined in the DNPNET.CONFIG.DNP_Client_Commands array, controlling binary outputs for relays etc uses Control Relay Object Block functions which are defined in DNPNET.CONTROL.CROB_Commands . All CROB functions can use... Read More
Shaded Areas in the Subset Definitions
Viewed 1 times since Tue, May 5, 2015
What do the shaded areas in the subset definitions indicate? - Objects that we support that are not required within the Level II specification are shaded. Refer to the associated notes to determine our response to the message. Read More
Changing the amount of data returned by class 0 polls as a server
Viewed 1 times since Mon, Sep 15, 2014
The amount of data the MVI56E-DNPNET returns, when functioning as a server and polled for all its data (class 0 poll) by a client is determined by the sizes of the DNPNET_DNP_Input_Database and the DNPNET_DNP_Output_Database UDTs (User-defined Data... Read More