KB Home | Advanced Search | News | Ask Question |
|
ProSoft Knowledge Base |
Do you have samples for your PTQ modules in ProWorx or ModSoft format? I see information for Concept and Unity, but nothing for ProWorx or any other programming environment.
Viewed 1 times since Tue, Jan 23, 2007
Per the recommendation of Schneider, we do not provide any samples for programming packages besides Concept and Unity. This does not mean that the module will not work in this environment; it just means there are no samples for this. Since the PTQ... Read More
Why am I unable to download my Config file to my PTQ module?
Viewed 1 times since Tue, Nov 28, 2006
The setup jumper must be off or unpinned in order for the module to accept a config file. Read More
Can my PTQ module be configured with Unity Pro software?
Viewed 1 times since Tue, Nov 28, 2006
All ProSoft PTQ modules are configured with the ProSoft Configuration Builder software that is provided with the module. PTQ modules will work with Modicon Quantum processors that have been programmed with ModSoft, ProWorxNxT, ProWorx 32, Concept,... Read More
What is the purpose of the battery on the PTQ modules?
Viewed 1 times since Tue, Nov 28, 2006
The battery is a lithium rechargeable type.The battery is used for the RTC (real-time clock) and CMOS RAM. Unless the customer changes the CMOS settings and afterwards the battery were to die, (after about 3 weeks) the CMOS settings would be lost and... Read More
How many PTQ modules can be added to a Quantum Rack?
Viewed 1 times since Tue, Nov 28, 2006
Each specific model of Quantum processor has a limit on how many Option modules are supported by that processor. PTQ modules are considered Option Modules, as are other communications modules, like RIO HEAD, NOM, NOE, and NOX Option modules. To... Read More
Are any ProSoft solutions SIL2 rated?
Viewed 1 times since Tue, Oct 14, 2008
Functional Safety “SIL” Rating Functional Safety is implemented in a system which performs, detects or reports safety functions from design processes in IEC 61508 and augmented under a QMS of ISO 9001. Safety functions of equipment... Read More
The order of bits in the Binary Inputs and Outputs of my PTQ-DNP module appear to be the opposite of what I expect. Why?
Viewed 1 times since Fri, Oct 10, 2008
When transferring Binary Inputs and Outputs to or from a Modicon Quantum CPU using the PTQ-DNP module, the bit pattern appears to be reversed, most-significant to least significant and vise versa. In other words, to set DNP BI point 0, you have... Read More
|
||||