Category Articles RSS Feed
What does a -36 modbus error code indicate?
Viewed 1 times since Thu, Aug 20, 2015
A negative thirty six (-36) error code is generated when we have successfully connected to a device and issued the device a Modbus request, but it has not responded to the request within the defined response time out period. This is akin to calling... Read More
What is Enron-Daniels mode?
Viewed 1 times since Thu, May 5, 2016
In some of our older Modbus products we had/have a feature called float flag. This feature, which has been renamed to Enron-Daniels mode in most of our newer Modbus products to avoid the misconception that this mode was necessary for accessing... Read More
When should I use an MVI56E-MNETCR?
Viewed 1 times since Fri, Sep 5, 2014
This multi-client Modbus TCP In-Chassis module has been designed for ControlLogix applications where the MVI56E-MNETCR is in a remote rack from the ControlLogix processor, and is linked to the processor chassis via ControlNet. This firmware has been... Read More