ILX56-PBS product photo

PROFIBUS DPV1 Slave for ControlLogix®

ILX56-PBS

The ILX56-PBS PROFIBUS DPV1 Multi-Slave module allows Rockwell Automation® ControlLogix® processors to communicate on a PROFIBUS DP protocol network by emulating up to 10 individual slave devices.

This multi-slave support of the module provides the ability to pass up to 2440 bytes of input and output data as high-speed cyclic I/O data on a PROFIBUS DP network.

Combined with the use of multiple I/O connections back to the ControlLogix processor, this module provides data update rates that will meet even the most demanding of PROFIBUS DP applications.

In addition, with the use of the PLX50 Configuration Utility you have advanced features such as custom-built Add-On Routines and a PROFIBUS DP packet capture utility to minimize the amount of time and effort in getting a ControlLogix PAC operating on a PROFIBUS DP network.

Architectures

Click on image(s) to enlarge
Drag with the mouse. Click for close.

Features and Benefits

  • Rockwell Automation Encompass™-Approved Solution
  • Remote diagnostics via configuration utility with built-in PROFIBUS DP packet capture utility
  • Multi-slave mode allows module to emulate up to 10 individual slaves for transfer of up to 2440 bytes of cyclic I/O data
  • Supports DPV1 Acyclic Messaging
  • Add-On Profile and custom Add-On Routines provided to allow for seamless integration to Studio 5000
  • Can emulate the PROFIBUS DP Identification number of the ProSoft MVI56-PDPS module to allow replacement of legacy modules without having to reprogram the PROFIBUS DP master device (Note: Requires ladder logic changes)

Specifications

PROFIBUS DP Slave Specifications

Specification

Description

Slaves

Emulate up to 10 individual slaves

Input/Output

Maximum 244 Bytes per Slave

Input Data

Maximum 2440 Bytes (244 per slave)

Acyclic Data

DPV1

Status data

88 Bytes

Output data

Maximum 2440 Bytes (244 per slave)

DPV1 Services

Class 1 Read/Write, Class 1 Alarm            

Services

Global-Control, Slave-Diagnostic, Set-Parameter

Sync, Freeze Command

Supported

Baud rate

9.6 kBaud, 19.2 kBaud, 45.45 kBaud, 93.75 kBaud, 187.5 kBaud, 500 kBaud, 1.5 MBaud, 3 MBaud, 6 MBaud, 12 MBaud.

Auto-detection mode is supported

Hardware

 

Specification

Description

PROFIBUS Interface

RS-485, Max. 12 Mbps, potential free, according EN 50170

Power Supply

450 mA @ 5Vdc

2 mA @ 24 Vdc

Dimensions

Standard 1756 Single-slot module

Burst

EN 61000-4-4, 2 kV, 5 kHz

Surge

EN 61000-4-5, 2 kV common mode, 1 kV differential mode

ESD

EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect

Radiated/Conducted Immunity

EN 61000-4-3, 10 V/m, 30...1000 MHz, 80% AM, 1 kHz sine wave
EN 61000-4-6, 10 V, 0,15...80 MHz

Radiated/Conducted Emission

EN 55011 Class A

Vibration/Shock (operating)

IEC 600068-2-6, 10-500 Hz, ± 0,75 mm, ± 2 g, 1 Octave/min

IEC 600068-2-27, 30 g, 11 ms

Operating Temperature

0°C  to 60°C (32°F to 140°F)

Relative Humidity

5 to 95% (non-condensing)

Certifications

ATEX Letter of Conformity 101.65 kB Last Modified 05/12/2022
CB Safety 335.02 kB Last Modified 04/03/2020
Declaration of Conformity (RoHS/CE) 547.35 kB Last Modified 12/18/2020
UL/cUL; Class 1, Div. 2 84.59 kB Last Modified 04/03/2020
Declaration of REACH Compliance 341.18 kB Last Modified 02/08/2021
Country Approval - Korea - KC Registration 281.11 kB Last Modified 03/18/2022
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1.92 MB Last Modified 07/10/2020