Can the module of MVI46-MCM be placed in Remote I/O Rack?
Viewed 1 times since Tue, Nov 28, 2006
The MVI46-MCM cannot be in a remote rack via blue hose (Remote I/O). However use of the module in "Extended local I/O" where the racks are connected using the chassis connector cable is supported. Read More
When my 2100-AGA is configured as a Modbus Master, the request packets being issued by the module are incorrect.
Viewed 1 times since Tue, Nov 28, 2006
The spacing in the MCM.CFG module configuration file and the MBM.CMD command file are critical. If the spacing of the text is not correct, the parsing of the configuration files will be incorrect, thus creating invalid outputs from the 2100-AGA... Read More
Can an MVI71-AFC or a 2100AGA module to work in a remote rack?
Viewed 1 times since Tue, Nov 28, 2006
The module will work in a local rack in any rack addressing mode (1/2, 1, or 2-slot mode as determined by the switch settings of the PLC5 rack). However, when installed in a Remote Rack, the module needs to communicate to the ASB using 2-slot... Read More
I have replaced my old 2100-AGA with PCMCIA Flash Card Slot with the newer style 2100-AGA with Compact Flash. Is there a way to edit the Modbus commands stored on the CF card without removing it from
Viewed 1 times since Wed, Mar 19, 2008
The older 2100-AGA solutions had keyboard, mouse, and monitor ports, so Modbus files could be edited on it.  That hardware became unavailable, so ProSoft had to create a substiute on different hardware that would be able to replace older 2100... Read More
What are the 2100-AGA Bios settings on the old hardware that has a VGA port, PCMCIA card, and 3 serial ports?
Viewed 1 times since Fri, May 7, 2010
That hardware was the EIP version of the 2100-AGA hardware.  This module required the bios settings listed in the attached document.  That hardware was later replaced by the 2100-AGA rev 3 module, using the same hardware as our MVI71... Read More