MVI69-Ethernet

GE Ethernet Global Data Network Interface Module for CompactLogix

MVI69-EGD

Limited Availability: Product with low inventory remaining. More Info

The MVI69-EGD Ethernet Global Data (EGD) module can be used to interface many different protocols with EGD devices. The EGD driver supports both the producer/consumer service port (18246) and the command service port (7937) using the UDP protocol over an IP network. The user defines the data to be produced and consumed in a configuration file downloaded to the module.

GE Fanuc Automation and GE Drive Systems developed an Ethernet Global Data, or EGD, exchange for PLC and computer data in 1998. Ethernet Global Data (EGD) offers versatility where a mix of control devices requires cooperation with each other. This involves sharing of information across the applications regardless of device or network type, often at high speed, and with high reliability. High reliability means fewer communication failures and having the ability to detect failures upon occurrence. Particular emphasis is delivered for applications requiring periodic or frequent updates and time synchronization of devices.

The protocol supports Unicast, Broadcast and Multicast group messaging. Efficiency is based on the fact that each device on the network can produce these types of messages and each device determines which of these messages to consume.

Features and Benefits

  • Single-slot - 1769 backplane compatible
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
  • Ladder Logic is used for data transfer between module memory and processor controller tags. A sample ladder file with AOI is included
  • Configuration data obtained from configuration text file downloaded to module. A sample configuration file is included.
  • Supports CompactLogix and MicroLogix 1500 LRP Controllers except 1769-QBFC1B, 1769-L16x, and 1769-L18x

Applications

Use the inRAx EGD module to connect various field devices using different networks or protocols, and share data between these devices over a wired connection. This is accomplished by exchanging shared common database information with the efficient but powerful Ethernet Global Data protocol.

Specifications

The driver interfaces with a common internal database in the module. This permits the sharing of data across many different networks.

The module supports UDP of service port 7927 (0x1F01) to handle all requests made of the module. The module will only service the requests and generate response messages. It will not generate command requests. The module supports the following functions specified in the EGD protocol:

Code

Description

3

Retrieve Configuration Request

4

Retrieve Configuration Response

7

Summary Request

8

Summary Response

9

Capabilities Request

10

Capabilities Response

15

Statistics Request

16

Statistics Response

18

Command NAK

32

Read Request

33

Read Response

34

Write Request

35

Write Response

36

Masked Write Request

37

Masked Write Response

The producer functionality provided in the EGD protocol is used to transfer portions of the module’s database to other EGD nodes on the network. The consumer functionality is used to transfer data from other nodes on the network into the module’s database.

The EGD module generates produced data as defined in the user configuration exchange list, from the module’s internal database, and is produced at the frequency defined in the exchange list. This data can be broadcast to all nodes or to a specific node on the network.

The EGD module consumes data as defined in the user configuration exchange list. This data is derived from other nodes on the network and is placed in the module’s internal database. If a consumer exchange is not received at the specified timeout, the driver will update the status of the exchange. When the driver again receives the exchange, the status will be updated.

Hardware

Specification

Description

Dimensions

Standard 1769 Single-slot module

Current Load

800 mA max @ 5 VDC
Power supply distance rating of 2 (L43 and L45 installations on first 2 slots of 1769 bus)

Operating Temp.

32° F to 140° F (0° C to 60° C)

Storage Temp.

-40° F to 185° F (-40° C to 85° C)

Relative Humidity

5 to 95% (without condensation)

LED Indicators

Power and Module Status
Application Status
CFG Port Activity
Ethernet Port Activity
Error Status

CFG Port (CFG)

RJ45 (DB-9M with supplied cable)
RS-232 only
No hardware handshaking

App Port (Ethernet modules)

10/100 Base-T Ethernet compatible interface
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991

Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

Shipped with Unit

RJ45 to DB-9M cables for each port
6-foot RS-232 configuration Cable

Certifications

ATEX Letter of Conformity 83.59 kB Last Modified 05/12/2022
CB Safety 347.28 kB Last Modified 02/26/2020
Declaration of Conformity (RoHS/CE) 531.65 kB Last Modified 12/18/2020
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1.92 MB Last Modified 07/10/2020
Korean KC Registration 584.13 kB Last Modified 03/13/2020
UL/cUL; Class 1, Div 2 (Canada) 1.14 MB Last Modified 02/27/2019
UL/cUL; Class 1, Div 2 232.99 kB Last Modified 04/08/2019
Declaration of REACH Compliance 340.56 kB Last Modified 09/08/2022