MVI56-Serial Picture

DNP 3.0 Master/Slave Network Interface Module for ControlLogix

MVI56-DNP

Limited Availability: Product with low inventory remaining. More Info

The DNP 3.0 Master/Slave Network Interface Module allows ControlLogix processors to interface with the many field devices that support the DNP protocol. DNP (Distributed Network Protocol) is an open communication protocol developed to achieve interoperability among systems specifically in the electric utility, oil & gas and water/wastewater industries. This non-proprietary protocol, available worldwide, was designed to optimize the transmission of data acquisition information and control commands. It is a highly efficient and reliable communications protocol between substation computers, RTUs, IEDs and master stations. DNP is also a layered protocol, featuring time stamping and True Report by Exception (TRBE). These features allow the MVI56-DNP module to send a report to the processor without being polled, providing real time data transmission in critical situations.

A conformal coating option is available for this product.

Features and Benefits

The module supports DNP Subset Level 2 features and some of the Level 3 features allowing the many SCADA and field devices supporting the DNP protocol to be integrated into the ControlLogix platform. The module acts as an input/output module between the DNP network and the ControlLogix processor. The data transfer from the ControlLogix is asynchronous from the actions on the DNP network. Databases are user defined and stored in the module to hold the data required by the protocol.

Specifications

  • Single Slot - 1756 backplane compatible
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
  • Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
  • Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
  • Local or remote rack

The module has two DNP protocol ports that can be user configured to operate in a Master/Slave or in a Slave/Slave redundant port configuration.

User defined internal register space is accessible to the protocol driver and to the ControlLogix processor memory.

Hardware

Specification

Description

Backplane Current Load

800 mA @ 5.1 VDC
3 mA @ 24 VDC

Operating Temperature

32° F to 140° F (0° C to 60° C)

Storage Temperature

-40° F to 185° F (-40° C to 85° C)

Shock

30 g Operational
50 g non-operational

Vibration

5 g from 10 to 150 Hz

Relative Humidity

5% to 95% (without condensation)

LED Indicators

Module Status
Backplane Transfer Status
Application Status
Serial Activity

Debug/Configuration port (CFG)

CFG Port (CFG)

RJ45 (DB-9M with supplied cable)
RS-232 only

Application ports (PRT1 & PRT2)

Full hardware handshaking control, providing radio, modem and multi-drop support

Software configurable communication parameters

Baud rate: 110 to 115,200 baud, depending on protocol

RS-232, 485 and 422

Parity: none, odd or even

Data bits: 5, 6, 7, or 8

Stop bits: 1 or 2

RTS on/off delay: 0 to 65535 milliseconds

App Ports (P1,P2) (Serial modules)

RJ45 (DB-9M with supplied cable)

RS-232 handshaking configurable

500 V Optical isolation from backplane

Shipped with Unit

RJ45 to DB-9M cables for each port

6-foot RS-232 configuration cable

Certifications

ATEX Letter of Conformity 79.81 kB Last Modified 05/12/2022
CB Safety 41.99 kB Last Modified 02/26/2020
Declaration of Conformity (RoHS/CE) 137.73 kB Last Modified 05/20/2022
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1.92 MB Last Modified 07/10/2020
Korean KC Registration 616.34 kB Last Modified 03/13/2020
UL/cUL; Class 1, Div 2 1.12 MB Last Modified 02/27/2019
UL/cUL; Class 1, Div 2 (Canada) 1.14 MB Last Modified 02/27/2019
Declaration of REACH Compliance 133.82 kB Last Modified 05/20/2022