Will ProSoft MVI69-xxxx solutions work with the new Allen-Bradley CompactLogix L23 series of processors?

are the power supply ratings for the currently available L23 series processors: 1769-L23-QBFC1B = 800mA at 5Vdc (1 MVI69-xxx will take all 800mA, no other modules could be used since MVI69-xxx will take all

Read more

How do I run the ProSoft Wireless Designer (PWD) software as an Administrator on Windows 7?

1.  From the Start Menu or PWD icon, right click and select Properties. 2.  Select the 'Compatibility' tab in the ProSoft Wireless Designer Properties window. 3.  Check the box 'Run this program

Read more

Why is the FTView application not getting any data from the AN-X2-AB-DHRIO Gateway running the RIO HMI firmware?

in FactoryTalk View: 1) Right click on Ethernet driver and select add new device 2)  Expand and browse the NetENI connected PCCC devices folder, and then expand and browse the PLC 5 processors folder

Read more

I am trying to use ProSoft Wireless Designer, version 2.1.3, and getting unknown or unresolved error messages. How do I fix this?

I am trying to use ProSoft Wireless Designer, version 2.1.3, and getting unknown or unresolved error messages. How do I fix this?

Read more

Read Commands from my Modbus Master to a ProSoft MCM Slave are working but Write Commands are failing. How do I fix this?

interpreted and appropriate responses sent. To activate this alternate timing scheme in older versions of ladder logic and ProLinx Gateways, set the UseGuardBand to "1" to enable this feature and set