Why am I unable to communicate with Wonderware from a 4xxx or 5xxx Series gateway in a full Duplex DF1 configuration |
| Article Number: 194 | Rating: Unrated | Last Updated: Fri, Jun 27, 2014 at 7:48 PM |
|
The Wonderware driver ABKF2 does not process or use the station ID when operating in Full Duplex mode. The DF1 full duplex specification requires a station id when more than one device is present on a network. A workaround has been implemented in our DF1 implementation. When the Local Station ID is set to 255 then the ProLinx will respond to all requests from the other device on the network. This change permits the gateway to successfully communicate with Wonderware when using the ABKF2 driver. |
Attachments (0)
There are no attachments for this article.
|
Comments
There are no comments for this article. Be the first to post a comment.
|
I am using a ProSoft DFCM solution (or possibly another DF1 protocol product) and I am having problems establishing and/or maintaining communications with a node that his been assigned Station Number
Viewed 1 times since Fri, Oct 10, 2008
What is the function of the "Delay Preset" in the Data Map section?
Viewed 1 times since Tue, Nov 28, 2006
Is there a limit, in a DF1 message, of the number of registers requested or written in 1 command?
Viewed 1 times since Tue, Nov 28, 2006
Bad Assignment error in Sycon software
Viewed 1 times since Tue, Nov 28, 2006
What does an error code of -200 (0xFF38) represent in my DFCM module?
Viewed 1 times since Tue, Nov 28, 2006
How do I transfer a floating point value using integer files in a MicroLogix1500?
Viewed 1 times since Thu, Apr 24, 2008
Can I configure my ProLinx 4xxx or 5xxx series gateway via Ethernet?
Viewed 1 times since Tue, Nov 28, 2006
Does the 4102 or 5102-MCM4-DFCM4 module have 4 Modbus ports and 4 DF1 ports (8 ports total)?
Viewed 1 times since Tue, Nov 28, 2006
I need to connect multiple DF1 devices to a single serial port on an SLC or MicroLogix processor, is there a solution?
Viewed 1 times since Tue, Nov 28, 2006
I have a xxxx-xxx-DFCM4 with Pass-Through enabled. The Pass-Through (Debug/CFG) port and the Port 0 DFCM port shows no activity. What am I doing wrong?
Viewed 1 times since Tue, Nov 28, 2006
|

Add Comment