| Home » Categories » Multiple Categories |
Why am I unable to communicate with Wonderware from a 4xxx or 5xxx Series gateway in a full Duplex DF1 configuration |
| Article Number: 194 | Rating: Unrated | Last Updated: Fri, Jun 27, 2014 at 7:48 PM |
|
The Wonderware driver ABKF2 does not process or use the station ID when operating in Full Duplex mode. The DF1 full duplex specification requires a station id when more than one device is present on a network. A workaround has been implemented in our DF1 implementation. When the Local Station ID is set to 255 then the ProLinx will respond to all requests from the other device on the network. This change permits the gateway to successfully communicate with Wonderware when using the ABKF2 driver. |
Attachments (0)
There are no attachments for this article.
|
Comments
There are no comments for this article. Be the first to post a comment.
|
What are the power requirements for the ProLinx and PLX communication gateways?
Viewed 1 times since Tue, Nov 28, 2006
What is the function of the "Delay Preset" in the Data Map section?
Viewed 1 times since Tue, Nov 28, 2006
Debug port connection parameters for Prosoft modules and gateways
Viewed 1 times since Tue, Nov 28, 2006
Why does the session time out when downloading a configuration file via HyperTerminal to my 4xxx or 5xxx Series ProLinx Gateway?
Viewed 1 times since Tue, Nov 28, 2006
Is there a limit, in a DF1 message, of the number of registers requested or written in 1 command?
Viewed 1 times since Tue, Nov 28, 2006
What product can be used to connect more than one DF1 master device to one or more DF1 slave devices?
Viewed 1 times since Tue, Nov 28, 2006
How do I transfer a floating point value using integer files in a MicroLogix1500?
Viewed 1 times since Thu, Apr 24, 2008
Does the 4102 or 5102-MCM4-DFCM4 module have 4 Modbus ports and 4 DF1 ports (8 ports total)?
Viewed 1 times since Tue, Nov 28, 2006
How to upload a configuration file from 4xxx or 5xxx Gateway?
Viewed 1 times since Tue, Nov 28, 2006
Can my ProSoft or ProLinx DFCM module communicate through an Allen-Bradley 1747-AIC module?
Viewed 1 times since Tue, Nov 28, 2006
|

Add Comment