Home » Categories » Multiple Categories |
How do I include or calculate a natural gas specific gravity value? |
Article Number: 436 | Rating: Unrated | Last Updated: Wed, Dec 31, 2014 at 4:59 PM |
If there is no analysis available, the user must supply in the meter configuration a suitable default relative density (= specific gravity), the density of the gas relative to air at the reference conditions.
If there is an analysis available (such as from a GC) then the AFC calculates the relative density (specific gravity) using AGA 8; any specific gravity coming from the GC is not used and not recorded.
The AFC has no ability to override the calculated SG with one entered from outside (e.g. from the GC), so any entered SG will not be used in calculations. If one wants to record the SG generated by the GC, he can use a little-known feature called Arbitrary event-logged value (see Modbus Dictionary for registers 90-99), but be aware that there are only 1999 events and if the GC delivers a new analysis every (say) 2 minutes then this event will fill up the event log in less than 3 days.
|
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
Downloading a new .AFC project file to an AFC flow computer module.
Viewed 1 times since Tue, Nov 28, 2006
For what purposes would I use the Multiple Meter Streams options on my MVIxx-AFC Flow Computer?
Viewed 1 times since Wed, Mar 19, 2008
Do ProSoft AFC Flow Computer solutions support "ASME MFc-6M", "API-11" and/or "API-12" calculation standards for measuring lubricating oils?
Viewed 1 times since Tue, Jul 8, 2008
Do ProSoft AFC Flow Computers support annubar-type flow sensors?
Viewed 1 times since Tue, Jul 8, 2008
How do I configure a vortex, ultrasonic or coriolis type meter in my AFC module?
Viewed 1 times since Tue, Nov 28, 2006
Using AFC modules with corrected (net) flow as in input
Viewed 1 times since Fri, Sep 19, 2014
Is it possible to configure an AFC flow computer solutions to use the ISO 6976 computation standard?
Viewed 1 times since Thu, Apr 24, 2008
Do the serial ports on my MVI56 module provide any electrical isolation?
Viewed 1 times since Tue, Nov 28, 2006
The Wallclock in my ProSoft MVIxx-AFC module seems to be showing Greenwich Mean Time (GMT or Universal Time) instead of Local Time. How do I get it to use Local Time?
Viewed 1 times since Wed, Dec 3, 2008
Where are the on-board jumper positions defined for my MVI module?
Viewed 1 times since Tue, Nov 28, 2006
|