When using an MVI69-xxx or PS69-xxx module, why does a L43/L45 CompactLogix processor fault immediately after a download or after a power cycle? |
Article Number: 438 | Rating: 5/5 from 1 votes | Last Updated: Wed, Jun 15, 2011 at 1:14 PM |
A firmware anomaly has been identified in version 17 for the CompactLogix 1768-L43 and L45 processor that will not work properly when using any Prosoft MVI69 or PS69 communication modules. FRN 18 will correct the issue.
Work around's are: Use earlier FRN (16 or earlier) or Clear the major non - recoverable fault and re-download the program a second time See also article #456 http://www.prosoft-technology.com/kb/article.php?id=456 for additional issue with PS69-DPM and PS69-DPS.
|
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
Is the MVI69 series of ProSoft modules compatible with the MicroLogix1500 processor?
Viewed 1 times since Tue, Nov 28, 2006
I have an In-Chassis module, and am seeing a type mismatch shown in the module properties. What is the issue?
Viewed 1 times since Fri, Apr 27, 2007
Debug port connection parameters for Prosoft modules and gateways
Viewed 1 times since Tue, Nov 28, 2006
My MVI69 module is not working. What might be wrong?
Viewed 1 times since Fri, Oct 10, 2008
IEC-60870-5-104 Server Tutorial
Viewed 1 times since Mon, Sep 3, 2012
Do ProSoft CompactLogix modules work with the new CompactLogix processors?
Viewed 1 times since Thu, Mar 5, 2015
RSLogix 500 sample for MVI69-xxx faults MicroLogix processor
Viewed 1 times since Tue, Nov 28, 2006
Will ProSoft MVI69-xxxx solutions work with the new Allen-Bradley CompactLogix L23 series of processors?
Viewed 1 times since Fri, Oct 31, 2008
|