I am unable to view the Debug Menu on my MVI71-DNP module.
Viewed 1 times since Tue, Nov 28, 2006
The MVI71-DNP User Guide states that you should configure your terminal emulation software to 57,600 baud, 8 data bits, no parity, 1 stop bit, no hardware handshaking. In MVI71-DNP configuration, there is a parameter that sets the baud rate for the... Read More
How do I deal with an unsigned integer in an SLC, PLC5, or MicroLogix processor?
Viewed 1 times since Tue, Jan 23, 2007
Scenario: A device that uses an INT value to represent a range of 0 to 65535, but in the processor the INT tag has a range of -32768 to 32767. Since the A/B processor does not have an unsigned Integer data type, you will need to convert this value... Read More
Debug port connection parameters for Prosoft modules and gateways
Viewed 1 times since Tue, Nov 28, 2006
Connect PC to module's debug / configuration port using a null-modem cable Start Hyperterminal, Putty or other comm program and use the following settings: bits per second: 57,600 data bits: 8 parity:... Read More
What is the difference between the 3100-MCM and the MVI71-MCM
Viewed 1 times since Tue, Nov 28, 2006
The MVI71-MCM is the latest Modbus module for the Allen-BradleyPLC5 platform. The MVI71-MCM provides a debug port which allows the user to view module configuration and status. The MVI71-MCM provides a built-in data analyzer for troubleshooting... Read More
When the MVI71-MCM is connected using Side-Connect, can a Modbus Master device read and write to the same Modbus address in the module?
Viewed 1 times since Tue, Nov 28, 2006
Yes, a Modbus master can read and write to the same address in the MVI71-MCM module when side-connect is used. In the configuration file, the read start and write start values should both be set to the same value (e.g. read start = 0, write start =... Read More
IEC-60870-5-104 Server Tutorial
Viewed 1 times since Mon, Sep 3, 2012
The following document outlines the ProSoft implementation of the IEC-60870-5-104 Server communication module as pertains to all -104S products.  Read More
Do you have an in-rack Ethernet I/P solution for a PLC-2 processor?
Viewed 1 times since Wed, Jan 21, 2009
Yes, the MVI71-DFNT can work in a 1771 chassis with a PLC-2 processor. Along with the MVI71-DFNT sample ladder, you will need to use the following settings in the PLC-2 programming software: *The Lengths of the BTW and BTR instructions should be... Read More